CT PT Analyzer HYVA-402V
	
	1  Turns Ratio, ratio error and phase error test
	2  Polarity test for CT
	3  Excitation curve and knee voltage measurement in power frequency for CT
	4  Error curve test
	5  Coil resistance test for CT and PT
	6  Secondary burden test for CT
	7  Turns ratio test for PT
	8  Polarity test for PT
	9  Excitation curve test for PT
	10 Coil resistance test for PT
	
	1  Output voltage:0~2000V(RMS)
	2  Test frequency: power frequency (50Hz/60Hz)
	3  Output Current:0~5A
	4  Maximum output power:2KVA
	5  Maximum knee voltage measurement: 2000V
	6  Range of turn ratio:
	   1~10000,error 0.5%RDG, 
	   10000~30000,error 1%RDG
	7  Range of voltage measurement: 
	   0~50V(RMS),error 0.5%RDG+0.05%FS
	   0~600V(RMS), error 0.5%RDG+0.05%FS
	   0~2000V(RMS), error 0.5%RDG+0.05%FS
	8  Range of current measurement: 
	   0~50mA(RMS),error 0.5%RDG+0.05%FS
	   0~1A(RMS), error 0.5%RDG+0.05%FS
	   0~5A(RMS),error 0.5%RDG+0.05%FS
	9 Test current of coil resistance:0.11A
	10 Test error of coil resistance: 
	     0~5 Ω, error 0.5%RDG+0.05%FS   
	     0~50Ω, error 0.5%RDG+0.05%FS  
	     0~100Ω,error 0.5%RDG+0.05%FS
	11 Test Current of secondary burden:0.11A(RMS)
	12 Test error of secondary burden:
	     0~5Ω, error 0.5%RDG+0.05%FS 
	     0~50Ω, error 0.5%RDG+0.05%FS
	     Power factor error:0.5%RDG+0.05%FS
	13 Power supply:AC220V±10% 50Hz/60Hz