CT PT Analyzer HYVA-404
	
	Tests for Current Transformer:
	 
	1  Excitation curve and parameters test
	2  Turns ratio test
	3  Ratio and phase error test
	4  Polarity mark check
	5  Winding resistance measurement
	6  Secondary loop burden measurement
	7  Error line curve test for protection CT
	8  Transient CT parameters test
	9  CT nameplate guess
	10  Saturation hysteresis loop curve measurement
	
		 
	
		Tests for Voltage Transformer:
	
		 
	
		1  Turns ratio test
	
		2  Ratio error and phase angle error test
	
		3  Polarity test
	
		4  Secondary burden test
	
		5  Winding resistance test
	
		
			 
		
			Applications of CT/ PT Analyzer:
		
			 
		
			1  CT nameplate check
		
			2  CT parameters check in work burden
		
			3  CT transient parameters analysis
		
			4  CT ratio and phase error calibration
		
			5  PT routine test
	 
 
	
	1  Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
	2  Power supply: AC220V±10%, 50/60Hz±10%
	3  Voltage output: 0.1~180V (AC)
	4  Current output: 0.001~5A(RMS)
	5  Power output: 500VA
	6  Maximum knee voltage measurement: 45KV
	7  Current measurement:
	    Range: 0~10A (automatically change range in 0.1/0.4/2/10A) 
	    Error: <±0.1%+0.01%FS
	8  Voltage measurement:
	   Range: 0~200V (automatically change range in 1V/10V/70V/200V)
	   Error: < ±0.1%+0.01%FS
	9  Turns ratio measurement:
	     Range:1~35000
	     1~2000     error<0.05%
	     2000~5000  error<0.1%
	     5000~35000  error<0.2%
	10 Phase measurement: error: ±2min; resolution: 0.01min
	11 Winding resistance measurement: 
	      Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
	      Error: < 0.2%RDG+0.02%FS
	      Maximum resolution: 0.1mΩ
	12 Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
	13 CT Secondary burden:
	      Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
	      Error: <0.2%RDG+0.02%FS 
	      Maximum resolution: 0.001ohm
	14 PT Secondary burden:
	      Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
	      Error :<0.2%RDG+0.02%FS 
	      Maximum resolution: 0.1ohm
	15 PT ratio measurement:
	      Range: 1~35000
	      1~10000 error<0.1%
	      10000~35000 error<0.2%
	16  PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%
	17  PT phase angle measurement: maximum error < 3min
	18  Make evaluation for test results according to selected standards
	19  Make word report for test result
	20  Make word reports one time for multi-group test records on the PC
	21  Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
	22  Compare excitation curves with saved excitation curves in the same window
	23  Memory capacity: >1000 groups test results
	24  Working condition: temperature: -10℃~50℃; moist: ≤90%